Maximum COP of Heat Pumps & Refrigeration Cycles

A maximum COP is meaningful only after the thermal service, system boundary, fixed and free variables, admissible cycles and objective are declared. For variable-temperature heat exchange, the full heat and temperature profiles matter.

Take the guided tourIllustrated overview

Summary

This article distinguishes an external reversible profile reference, a cycle-constrained reversible reference and an equipment-constrained optimum. It derives a two-duty COP relation from energy and reversible entropy balances, then compares four illustrative T–Q configurations. The relation depends on the declared system boundary, heat contacts and feasibility. The sketches and linked calculated examples do not establish a universal maximum COP for a real machine.

At a glance

  • Question: which boundary and admissible class define the maximum?
  • Method: energy and entropy balances for declared heat interactions.
  • Limit: local matching and equipment feasibility need separate assessment.

1. Three reference scopes

01

External reversible profile

The specified source and sink thermal service sets a reversible reference when an admissible, locally matched arrangement exists. It may require more than a single-stage machine.

02

Cycle-constrained reversible reference

A working fluid, process sequence, state connections and heat-contact conditions restrict the allowable reversible constructions. This reference can differ from the external profile benchmark.

03

Equipment-constrained optimum

Finite heat-exchanger approach, efficiency losses, throttling, pressure drop and auxiliary work enter the design optimization. It depends on equipment and operating conditions.

The term maximum must identify the class over which COP is maximized. Equality of aggregate entropy transfers is a necessary closure condition for a reversible two-contact reference, but does not establish local matching, a realizable machine or uniqueness.

2. How the reversible relation is formed

For a work-driven cyclic system with two declared heat-interaction groups, take QH as useful delivered heat and QC as absorbed heat, both positive magnitudes. First-Law closure gives W = QH − QC. If every contact is reversible and the model is feasible, the entropy transfers satisfy:

ΣH=∫HδQHTH=∫CδQCTC=ΣC

Define the entropic mean temperatures for the two heat-interaction groups:

TH*=QHΣHTC*=QCΣC

The corresponding two-duty reversible heating and refrigeration COPs become:

COPH,rev=QHW=TH*TH*−TC*COPC,rev=COPH,rev−1

Heating COP takes delivered heat as its useful output; refrigeration COP takes absorbed heat as its useful cooling output. Both use net work at the same declared boundary.

For sensible streams with constant heat-capacity rate, the entropic mean equals the logarithmic mean of the absolute endpoint temperatures. A simple arithmetic endpoint mean is generally an approximation. The integral form also admits nonlinear profiles if their actual heat and temperature record is known.

3. Four illustrative T–Q configurations

These are schematic, independently aligned high- and low-temperature heat interactions, not a time-ordered cycle path. Red is delivered high-temperature heat; blue is absorbed low-temperature heat. Both branches in each panel begin at |Q| = 0 on the same increasing scale, without numerical tick values. Solid curves show working-fluid paths except in the Lorenz-type panel, where they show independent external streams. In these four sketches, dashed curves show external streams where present; a dashed connector in a combined cycle-library T–Q view has a different meaning. For the illustrated two-duty cyclic boundary with positive net work input, the longer red span represents QH = QC + W. A working-fluid path and its corresponding external stream have equal heat-duty spans at the depicted contact. Horizontal positions on the high and low branches do not imply paired exchanger locations. The duty ratio and endpoints are qualitative, not calculated.

Isothermal refrigerant contacts

Horizontal idealized working-fluid heat contacts and sloping external water profiles|Q| per interaction (schematic)Temperature T
High-temperature heatLow-temperature heatSolid: R290 working fluidDashed: external streams

Solid horizontal lines represent idealized pure-refrigerant condensation and evaporation; dashed sloping lines represent external sink and source water. A conventional Carnot value with two isothermal contact temperatures applies to that restricted contact model. R290 compression with throttling is not itself reversible.

Reversed Brayton

Two sloping reversed Brayton working-fluid heat paths in a constant-property ideal-gas model|Q| per interaction (schematic)Temperature T
High-temperature heatLow-temperature heatSolid: N₂ working fluid

Solid lines show two internal ideal-gas isobars under a constant-property teaching model. The simple COP = τ/(τ − 1) also requires the coupled ideal Brayton state ratios and isentropic connections; equal glide slopes by themselves are insufficient. External stream profiles are not drawn.

Unequal finite-stream glides

Two unequal straight external stream temperature profiles, a schematic finite-stream comparison|Q| per interaction (schematic)Temperature T
High-temperature heatLow-temperature heatSolid: External streams

Solid lines show two different external temperature glides. A locally matched, reversible finite-stream Lorenz-type reference is one possible comparison. The library’s calculated polytropic Lorenz example is a heat engine analogy with unequal internal T–Q slopes, not a solved Lorenz heat pump.

Transcritical CO₂ / R744

Curved CO₂ gas-cooler path above an illustrative sink-water profile, with nearly isothermal evaporation below a source profile|Q| per interaction (schematic)Temperature T
High-temperature heatLow-temperature heatSolid: CO₂ / R744 working fluidDashed: external streams

The solid curved red line represents a qualitative gas-cooler path; dashed red represents changing sink water temperature. Solid blue represents near-isothermal CO₂ evaporation, with the dashed blue external source profile above it. The bounded R744 cycle model calculates states and heating/cooling COP for selected inputs. This sketch is qualitative; the model does not optimize high pressure, calculate external local matching or establish a maximum COP.

4. Fixed data, free variables and feasibility

Four water inlet and outlet temperatures together with both heat-capacity rates specify both heat duties for a constant-property sensible-stream model. They also determine W through the First Law. COP cannot then be varied independently while holding all those inputs fixed. If a source outlet temperature, flow rate or duty is free, solve the revised problem with that choice explicitly stated.

A single-stage reversed Brayton cycle has coupled temperature ratios, such as T₂/T₁ = T₃/T₄ = τ in the stated ideal model. Arbitrary external terminal temperatures may not admit zero-approach matching by that architecture. An external reversible profile reference may require another permissible architecture, multiple stages or a cascade. An optimization must distinguish a feasible maximum from an upper bound or a supremum approached only in a limiting construction.

5. Thermal Matching and technical COP

Finite temperature differences during nonzero heat transfer generate entropy. A working-fluid temperature glide that follows the source and sink more closely can reduce one source of irreversibility. The direction and size of a real COP change must be evaluated with fluid properties, local pinch, heat-transfer coefficients, compressor work, pressure loss and equipment constraints.

The same framework can describe water–water, air–water, water–air, air–air and refrigeration duties only when the necessary stream states and boundaries are supplied. Humid air, condensation, frost, phase change and combined latent and sensible loads require their respective material and property balances. Four dry-bulb temperatures alone do not specify them.

6. Explore the models and background

Cycle Library and tools →External Heat Exchange →Reversible Solution Spaces →Reversible Cycle Benchmark →Scientific literature review (available on request) →

The equations and energy/entropy balances are established thermodynamics under their stated assumptions. The three-scope teaching organization and its software presentation are CarnotX’s proposed operational framing. The schematic figures are not experimental results or independent validation of a complete COP Max solver.